Modular data center steel framing is the welded or bolted structure that turns a factory-built module into something that can be lifted, trucked and set on a foundation without racking or cracking. It is usually built from structural shapes such as wide flange beams, channel and angle, plus rectangular structural tube and plate, and it has to carry equipment loads in service as well as the very different loads of lifting and transport.
The appeal of modular construction is speed and repeatability: IT halls, power rooms and cooling plant are assembled and tested in a factory while the site is prepared. That only works if every frame in the program comes out the same, which puts the fabricator’s process at the center of the schedule.
What gets built as a module
“Modular data center” covers a range of products, from a single containerized IT unit to a campus built from dozens of prefabricated blocks. The steel structure changes with each type.
| Module type | What it contains | Framing characteristics |
|---|---|---|
| IT or white space module | Racks, containment, cooling units | Floor frame sized for rack loads, roof framing for cable tray and busway |
| Power skid or electrical house | Switchgear, UPS, transformers, distribution | Heavy base frame with concentrated equipment loads and lifting lugs |
| Cooling skid | Chillers, pumps, heat exchangers, piping manifolds | Open structural frame with equipment supports and drip containment |
| Containerized unit | Complete small data center or edge site | ISO container format with corner castings and reinforced openings |
| Prefabricated overhead superstructure | Cable tray, busway, containment and lighting supports | Light frames or strut assemblies hung from the building structure |
Many projects mix approaches: a conventional building shell with prefabricated power and cooling skids outside and prefabricated overhead supports inside the data hall.
Framing members and materials
Module frames use familiar structural steel, chosen for strength, availability and ease of welding.
- Wide flange beams to ASTM A992 form base frames and long-span members where bending loads are high. Our A36 vs A992 comparison explains why A992 is the standard for W shapes.
- Channel and angle in A36 frame floors, edges, bracing and equipment supports. Channel works well as a perimeter member because its flat back gives a clean face for cladding and connections.
- Rectangular and square structural tube, commonly specified to ASTM A500, gives columns and bracing good torsional stiffness in a light section, which helps a module resist twisting when it is lifted.
- Plate in A36 makes base plates, gusset plates, lifting lugs, splice plates and equipment pads.
- Sheet in cold rolled, galvanized or galvannealed steel covers floors, walls and roofs on enclosed modules.
Outdoor skids and modules need corrosion protection suited to the site, such as a high-performance paint system or hot-dip galvanizing after fabrication to ASTM A123. Members inside a conditioned building are usually primed and painted or powder coated.
Design loads and codes
A module frame is designed for more load cases than a typical building member, because it lives three lives: in the factory, on the truck and on the site.
| Load case | What governs |
|---|---|
| In service | Dead load of the structure, equipment and rack loads, floor live load, roof loads, wind and seismic per ASCE 7 and the building code |
| Lifting | Lift point location, sling angles, dynamic factors and local stresses at lugs and corner fittings |
| Transport | Road shock and vibration, tie-down forces, support points on the trailer |
| Installation | Bearing on piers or slab, leveling, connections between adjacent modules |
Structural design is typically done to AISC 360, the Specification for Structural Steel Buildings, with welding to AWS D1.1 for steel. Lifting devices may also be designed to ASME B30.20 and ASME BTH-1 where the lugs or spreader beams are treated as below-the-hook lifting devices. The engineer of record sets these requirements; the fabricator’s job is to build exactly to the approved drawings and weld procedures.
Tip: Settle lift point locations and the rigging plan before frame drawings are released. A lifting lug moved late in design can mean new gussets, a different base beam and revised welds on every module in the order.
Connections, tolerances and shipping limits
Welded versus bolted
Base frames are usually fully welded in fixtures, which makes them stiff and keeps them square. Columns, roof frames and module-to-module joints are often bolted so modules can be split for shipping and joined on site. Bolted connections need accurate hole location; a pattern that is off by a small amount on one module can stop it from lining up with its neighbor.
Holding dimensions over a long frame
Module frames can be 40 ft (12.2 m) or longer, and welding heat shrinks and bows long members. Fabricators control this with welding sequence, fixtures, pre-set and measuring diagonals before parts leave the fixture. Fabrication tolerances for structural steel are commonly taken from the AISC Code of Standard Practice unless the drawings call for tighter values, and module programs often do. Our guide to metal fabrication tolerances covers how tolerances are specified.
Shipping envelope
Truck transport sets the outer dimensions. Under federal rules the standard maximum vehicle width on the national highway network is 8.5 ft (102 in), and loads wider or taller than legal limits need permits that vary by state, with escorts and travel restrictions for larger loads. Designers therefore size modules to the shipping envelope first and the equipment second, or plan to ship in sections.
Fabricating modular frames in volume
A modular program is closer to manufacturing than to one-off structural work. The same frame may be built many times, so the investment goes into setup: nested cutting programs, dedicated fixtures and repeatable weld procedures.
- Cutting and coping: beams and channels are sawn to length, coped and drilled; plate parts such as gussets and base plates are cut on CNC plasma or oxy-fuel tables.
- Tube processing: a tube laser cuts tube to length with holes, slots and end profiles in one setup, so tube members fit together with less hand fitting. See our article on tube laser cutting.
- Welding: fixtures hold members in position while welders or robotic cells complete the joints in a set order.
- Finishing and kitting: frames are blasted and coated, and loose parts such as clip angles, splice plates and hardware are kitted by module so the assembly line has everything it needs.
Revision control matters as much as weld quality. When equipment vendors change a footprint, every affected part, program and fixture has to change together, and the fabricator needs a clear cutover point so frames from old and new revisions are not mixed.
How ASA supports modular data center framing
American Steel & Aluminum stocks A36, A992, A709 and A588 structural shapes, structural tube and plate, and processes them in house with sawing and miter cutting, beam drilling and coping, CNC plasma and oxy-fuel plate cutting, tube laser cutting and manual and robotic welding. Kitting, kanban and just-in-time delivery on our own trucks support repeat module builds across New England and New York, with mill certifications and full material traceability available. Learn more about our steel processing capabilities.
Frequently asked questions
What steel is used for modular data center frames?
Most frames combine ASTM A992 wide flange beams for main members, A36 channel, angle and plate for secondary members and connections, and rectangular structural tube for columns and bracing. Enclosed modules add cold rolled, galvanized or galvannealed sheet for floors, walls and roofs. The structural engineer selects grades and sizes based on equipment loads, spans and lifting design.
Are modular data center frames welded or bolted?
Usually both. Base frames are commonly welded in fixtures because welding gives a stiff, square foundation for heavy equipment. Columns, roof members and connections between modules are often bolted so that modules can be shipped in pieces and joined on site. The split between welded and bolted joints is set by the design and the shipping plan.
How big can a modular data center module be?
Size is limited mainly by transport. The standard legal width for trucks on the national highway network is 8.5 ft, and wider or taller loads need state permits and may need escorts or route restrictions. Many modules are built at or near container dimensions for that reason, while larger units are shipped as oversize loads or in sections.
What is a power skid in a data center?
A power skid is a prefabricated steel base frame carrying electrical equipment such as switchgear, UPS modules, transformers or distribution panels, wired and tested in a factory before delivery. The skid frame must handle concentrated equipment loads, lifting and transport, and it often sits outdoors, so it needs lifting lugs, a stiff base and a durable coating.
Do modular data center frames need special welding certifications?
Requirements come from the project specifications. Structural steel welding is commonly performed to AWS D1.1 with qualified procedures and welders, and the engineer may require inspection, nondestructive testing or third-party review of critical welds such as lifting lugs. Buyers should list the welding code, inspection level and any documentation needed in the purchase order.