Battery Rack Manufacturing: Materials, Tolerances and Finishes

How steel battery racks for energy storage, UPS and telecom systems are built, from material and gauge choices to the tolerances and finishes that make modules fit.

Updated October 2026 5 min read By the ASA team

On this page
  1. Types of battery racks
  2. Materials and gauges
  3. Loads, stability and seismic design
  4. Tolerances that make modules fit
  5. Finishes, insulation and grounding
  6. Producing battery racks at volume
  7. How ASA supports battery rack manufacturing

Battery rack manufacturing turns steel sheet, tube and structural shapes into the frames that hold battery modules in energy storage systems, UPS rooms and telecom sites. Most racks are cold rolled or galvanized steel that is laser cut, formed on a press brake and either welded or bolted together, then powder coated. The hard parts are carrying dense, heavy modules safely and holding hole and slot positions accurately enough that every module, busbar and cable lands where the design says it will.

A battery rack is not the same as the enclosure around it. The enclosure keeps out weather and contains fire risk; the rack is the internal structure that positions and supports the batteries. Our guide to BESS enclosures covers the housing side.

Types of battery racks

Rack design follows the battery chemistry, the application and the installation environment.

Rack typeTypical applicationConstruction
Module rack for lithium-ion BESSContainerized and cabinet energy storageTall uprights with rails or shelves for slide-in modules, integrated busbar and cable paths
Open frame UPS battery rackData center and facility UPS roomsSingle or multi-tier frames for VRLA or lithium batteries, often bolted
Stepped or tiered rackLarge lead-acid stringsStaggered shelves so each cell is accessible for maintenance
Seismic rackSites in high seismic zones, telecom central officesHeavier members, cross bracing and anchorage designed to a seismic requirement
Battery cabinetIndoor UPS and telecomEnclosed rack with doors and side panels, frequently lockable

Materials and gauges

Steel dominates battery racks because it is stiff, strong, weldable and economical at volume. The choice of grade and coating comes down to load, environment and whether the rack is painted.

MaterialSpecificationWhere it is used
Cold rolled steelASTM A1008Shelves, rails, brackets and panels that will be powder coated
Hot rolled steelASTM A1011Heavier uprights, base frames and anchor plates
High-strength low-alloy (HSLA) sheetASTM A1008 or A1011 HSLAS gradesUprights and rails where higher strength allows lighter gauges
Galvanized or galvannealed steelASTM A653Parts left unpainted or exposed to humidity; base for duplex coatings
Aluminum 5052ASTM B209Lightweight trays, covers and module carriers

HSLA grades are worth considering on tall racks. A higher yield strength lets a designer carry the same load with thinner uprights and rails, which cuts weight for shipping and for floor loading. See our overview of HSLA steel for typical grades and properties.

Uprights and load-bearing rails are often 12 to 14 gauge, shelves and module rails 14 to 16 gauge, and covers lighter still, but these are typical ranges only. The rack engineer sets the gauge from the load analysis and the module supplier’s mounting requirements.

Loads, stability and seismic design

Battery modules pack a lot of mass into a small footprint, and lead-acid systems are heavier again for the same stored energy. A rack has to carry that weight without sagging shelves, buckling uprights or tipping, and it often has to do so through an earthquake.

  • Shelf and rail deflection. Excess deflection misaligns modules and stresses busbar connections. Formed returns and hems stiffen rails more efficiently than heavier sheet.
  • Upright buckling and frame stiffness. Tall racks need cross bracing or welded frames to resist sway, especially when modules are loaded unevenly during installation or service.
  • Anchorage. Floor anchors, base plates and top bracing transfer seismic and tipping loads into the building. Their design comes from the structural engineer, commonly working to ASCE 7 and the building code.
  • Telecom requirements. Telecom battery racks are frequently specified to Telcordia GR-63-CORE, which defines earthquake zones and test levels for network equipment frames.

Welded frames are stiffer and hold their geometry, while bolted knock-down designs ship flat and assemble on site. Many programs weld subassemblies such as side frames and bolt them together in the field.

Tolerances that make modules fit

Rack tolerances are driven by what has to line up across the whole structure: module slots, mounting holes, busbar connection points, cable tie points and the pitch between levels.

Prints usually apply a general tolerance block to non-critical dimensions and call out tighter limits on the features that matter. ISO 2768-1 is a common general tolerance standard on metric drawings. Its medium class (ISO 2768-m) sets these limits for linear dimensions:

Nominal lengthISO 2768-m tolerance
Over 6 to 30 mm (0.24 to 1.18 in)plus or minus 0.2 mm (0.008 in)
Over 30 to 120 mm (1.18 to 4.72 in)plus or minus 0.3 mm (0.012 in)
Over 120 to 400 mm (4.72 to 15.75 in)plus or minus 0.5 mm (0.020 in)
Over 400 to 1,000 mm (15.75 to 39.37 in)plus or minus 0.8 mm (0.031 in)
Over 1,000 to 2,000 mm (39.37 to 78.74 in)plus or minus 1.2 mm (0.047 in)

Those are general limits from the standard, not the values every rack needs. Module mounting holes and busbar points are usually given position tolerances relative to a datum so that error does not accumulate up the height of the rack. A slot pitch that is off by a small amount at each level can leave the top module noticeably out of position. Our article on metal fabrication tolerances explains how to specify them.

Tip: Cut all holes in a rail or upright in one laser setup and form it afterward, and keep holes away from bend lines. Holes cut in a single setup share a reference, and holes too close to a bend will distort when the part is formed.

Finishes, insulation and grounding

Powder coat is the standard finish for battery racks. It covers formed and welded parts evenly, resists chipping and comes in the black, gray and white colors most OEMs use. For racks in humid spaces or outdoor enclosures, powder coat over galvanized or galvannealed steel adds a second layer of protection.

Two electrical issues shape the finish plan:

  • Grounding. Metal racks are bonded to the equipment grounding system, so grounding studs and contact areas are masked before coating or cleaned to bare metal afterward.
  • Insulation. Paint is not treated as reliable electrical insulation. Electrical codes, including NEC Article 480 for storage batteries and Article 706 for energy storage systems, address battery supports, and for some battery types the code calls for nonconducting supports or continuous insulating material other than paint where cells contact conductive members. Module suppliers often specify insulating pads, liners or isolators as well.

Lead-acid installations add electrolyte exposure, so coatings for those racks are often chosen for acid resistance. Lithium-ion module racks in climate-controlled enclosures mainly need a durable finish and clean bonding points.

Producing battery racks at volume

Energy storage programs can call for racks by the hundreds, timed to cell and module deliveries. A typical production flow is fiber laser cutting of rails, uprights and brackets; press brake forming; tube laser cutting where frames use tube; robotic welding of repeat subassemblies in fixtures; powder coating; and kitting so each rack ships with its full set of parts and hardware.

Programs run smoothest when the design is frozen before production, first articles are measured against the module supplier’s interface drawing, and revisions are controlled so mixed-revision parts never reach the integration floor.

How ASA supports battery rack manufacturing

American Steel & Aluminum manufactures battery racking, frames and enclosures domestically, stocking cold rolled, hot rolled, HSLA, galvanized and galvannealed steel and 5052 aluminum and processing it with fiber laser cutting, CNC press brakes, manual and robotic welding and powder coating. For repeat programs, ASA can kit each rack’s parts and hardware and deliver on a kanban or just-in-time schedule, with mill certifications and full material traceability available. See our energy storage manufacturing capabilities.

Frequently asked questions

What material are battery racks made of?

Most battery racks are made of steel: cold rolled sheet for powder coated shelves and rails, hot rolled or HSLA steel for heavier uprights and bases, and galvanized or galvannealed sheet where parts stay unpainted or face humidity. Aluminum is used for lighter trays and covers. The choice depends on load, environment, finish and cost targets for the program.

Are battery racks welded or bolted?

Both designs are common. Welded racks are stiffer and keep their geometry, which helps module alignment, but they ship as large assemblies. Bolted racks ship flat and are assembled on site, which lowers freight cost. Many manufacturers weld subassemblies such as side frames in fixtures and bolt those together during installation or final integration.

Do battery racks need seismic certification?

It depends on the site and the market. Racks in seismic regions are typically designed and anchored to the building code and ASCE 7, and telecom battery racks are often specified to Telcordia GR-63-CORE earthquake zones. The structural engineer or equipment specification sets the requirement, and testing or calculations are provided for the specific rack design.

Can powder coat insulate a battery rack?

Powder coat should not be relied on as electrical insulation. It can chip, wear through at contact points and vary in thickness, and electrical codes do not generally treat paint as an insulator for battery supports. Where insulation is required, designers use nonconducting pads, liners, isolators or insulated rails specified by the battery or module supplier.

What tolerances do battery racks need?

General dimensions are often held to a standard tolerance block, such as ISO 2768 medium on metric drawings, while module mounting holes, slot pitch and busbar connection points carry tighter position tolerances from a common datum. The module manufacturer's interface drawing usually drives those critical values, so share it with the fabricator at the quoting stage.

Material, processing and fabrication from one supplier

Send a drawing or a material list and the ASA team will quote it from stock.